Calculators / Power and wiring
What size wire do you need?
Put in the load, the voltage and how far it is from the panel. You'll get the smallest wire that carries the breaker and keeps the voltage drop under 3%.
Updated · How we check our numbers
Use this wire
6 AWG copper
On a 60 A breaker. It carries 65 A, and drops 1.2% over 60 ft.
- Load
- 48 A× 1.25 continuous = 60 A
- Breaker
- 60 A
- Run
- 60 ft one way
Estimate for planning only, not professional advice. Check the manufacturer’s instructions, your local code and a licensed professional before you buy, build or install. Use at your own risk. Terms.
breaker = 48 A × 1.25 = 60 A → 60 A standard
smallest copper wire that carries 60 A at 75 °C = 6 AWG (65 A)
drop = 2 × 60 ft × 0.491 Ω/1,000 ft × 48 A = 2.8 V = 1.2% of 240 V
Copper, THHN/THWN wire in conduit
75 °C column, 240 V- 14 AWGcarries 15 A, drops 18.1 V (7.5%)Under 60 A
- 12 AWGcarries 20 A, drops 11.4 V (4.8%)Under 60 A
- 10 AWGcarries 30 A, drops 7.1 V (3%)Under 60 A
- 8 AWGcarries 50 A, drops 4.5 V (1.9%)Under 60 A
- 6 AWGcarries 65 A, drops 2.8 V (1.2%)Use this
- 4 AWGcarries 85 A, drops 1.8 V (0.7%)Also works
Ampacity from NEC Table 310.16, small wires capped by 240.4(D). Resistance from NEC Chapter 9 Table 8, at 75 °C.
This assumes 86 °F around the wire and no more than 3 current-carrying wires together. A hot attic, or cables bundled through the same holes, can need a bigger size.
A new 240 V circuit takes a permit in most towns, and your local code has the final say. Use this to plan and price the job, then have it inspected.
How we work it out
Two things size a wire, and the bigger answer wins.
Ampacity. The wire has to carry the breaker that protects it. A load that runs 3 hours or more, like an EV charger or a heater, is sized at 125%, then rounded up to a standard breaker. We take the ampacity from NEC Table 310.16. NM-B and UF-B cable must use the 60 °C column; THHN in conduit uses 75 °C, the most a breaker terminal is rated for. 14, 12 and 10 AWG copper are capped at 15, 20 and 30 A.
breaker = load amps × 1.25 if continuous, up to the next standard size
Voltage drop. Current goes out and back, so the wire is twice the run. The NEC suggests keeping a branch circuit under 3%. We use each size's resistance at 75 °C from NEC Chapter 9 Table 8.
drop = 2 × one-way feet × ohms per 1,000 ft × amps ÷ 1,000
Not counted: hot attics over 86 °F, more than 3 current-carrying wires bundled together, and feeders. Those can push you a size bigger. Your local code and inspector have the final say.
Where the numbers come from
- NFPA 70 (NEC), free access edition
- Encore Wire: ampacity table (NEC 310.16) and 240.4(D) limits
- Southwire: Romex SIMpull NM-B spec, 60 °C ampacity (2023 NEC)
- Southwire: SIMpull THHN/THWN-2 spec, 75 and 90 °C ampacity (2023 NEC)
- Okonite Engineering Handbook: conductor resistance and temperature correction
- Cerrowire: 3% voltage drop table
Guides
Sizing the load first
More calculators
- Watts to ampsHow many amps is this, and what breaker does it need?
- Air compressor sizingHow much airflow do my air tools need?
- Generator sizingWhat size generator runs what I need?
- EV charger installWhat does a Level 2 charger cost, and can my panel take it?
- Home battery backupHow many home batteries do I need?
- Power station runtimeHow long will a power station run my fridge?
- Ah to WhHow many watt-hours is my battery?
- Off-grid solarWhat panels, battery and controller for my RV or cabin?