Calculators / Batteries and solar

What off-grid solar system do you need?

Put in what you use a day and how much sun you get. You’ll get the panels, the battery bank and the charge controller, sized with the makers’ own rules.

Updated · How we check our numbers

These are example numbers. Put in yours.

Your power

Wh

Each device’s watts × hours a day, added up. A 60 W fridge average is 1,440 Wh a day.

h

Hours of full sun a day in your worst month. Winter in the northern US can be 2 to 3.

The system

System voltage
Battery
days

Morningstar: 4 to 5 days in many places; 2 to 3 with a generator backup.

The panels

W
V

On the panel’s datasheet or label.

%/°C

Negative, on the datasheet: often −0.24 to −0.3.

°F

Panel voltage rises in the cold. Use your record low.

Your off-grid system

4 × 430 W, 469 Ah

1,720 W of panels, a 469 Ah battery bank at 24 V (11.3 kWh), and a 60 A MPPT controller, for 3,000 Wh a day.

Panels
1,720 W4 × 430 W
Battery
469 Ah11.3 kWh at 24 V
Controller
60 A
See MPPT charge controllers on Amazon (opens Amazon in a new tab)

As an Amazon Associate we earn from qualifying purchases.

Estimate for planning only, not professional advice. Check the manufacturer’s instructions, your local code and a licensed professional before you buy, build or install. Use at your own risk. Terms.

array = 3,000 Wh × 1.2 × 1.2 ÷ 3 h = 1,440 W

bank = 3,000 Wh × 3 ÷ 0.8 ÷ 24 V = 469 Ah

controller = 1,720 W ÷ 28.8 V = 59.7 A

cold Voc = 38.91 V × (1 + -0.24% × (-17.8 − 25 °C)) = 42.9 V

What to buy

24 V system
  • 4 panels1,440 W needed: 3,000 Wh × 1.2 × 1.2 ÷ 3 sun hours
    1,720 W
  • Battery bank3,000 Wh × 3 days ÷ 80% usable = 11,250 Wh
    469 Ah at 24 V
  • Charge controller (MPPT)1,720 W ÷ 28.8 V charging
    60 A
  • Panels in series on a 100 V controller42.9 V per panel at 0°F (Voc 38.91 V)
    up to 2
  • Panels in series on a 150 V controller42.9 V per panel at 0°F (Voc 38.91 V)
    up to 3
  • Panels in series on a 250 V controller42.9 V per panel at 0°F (Voc 38.91 V)
    up to 5

Morningstar, Renogy and Victron sizing rules. A design check, not an engineered system.

Use the worst month

Peak sun hours are the hours of full sun the day’s light adds up to. Morningstar sizes an off-grid array for the month with the least sun, so use your winter figure, not the yearly average, if you need power year round.

How deep to go

We count 80% of a lithium bank as usable (Renogy: “Do not exceed 80%”). Battle Born rates its batteries for 100%, which would shrink the bank by a fifth.

Picking the controller

Choose the next size up from 60 A. Victron allows up to 130% oversizing on its MPPT controllers, but don’t exceed the controller’s maximum PV voltage, below.

How we work it out

panels (W) = daily Wh × 1.2 × 1.2 ÷ peak sun hours

Morningstar sizes an off-grid array to make at least 115 to 120% of the daily load in the month with the least sun, then about 20% more on top of that. Use your winter sun hours if you need power all year.

battery (Ah) = daily Wh × days of autonomy ÷ usable share ÷ system volts

Morningstar suggests 4 to 5 days of autonomy in many places, 2 to 3 with a generator. Only part of a bank is usable: half of a lead-acid battery (Morningstar), and we count 80% of lithium (Renogy; Battle Born rates 100%).

controller (A) = panel watts ÷ charging volts · cold Voc = Voc × (1 + β × (T − 25 °C))

Renogy's formula, at 14.4, 28.8 or 57.6 V charging. Panels make more voltage in the cold, so the number you can wire in series is set by your coldest morning and the controller's maximum PV voltage, as Victron warns. The default panel is a Silfab SIL-430 QD.

Solar output by ZIP comes from PVWatts v8, from the National Laboratory of the Rockies (formerly NREL). The laboratory provides the data as is, without warranty, and doesn't endorse this calculator.