Wire gauge chart

From the NEC ampacity table, checked against wire makers' published copies. Your inspector has the final say.

Short answer

14 AWG copper goes on a 15 A breaker, 12 AWG on 20 A and 10 AWG on 30 A. 6 AWG copper is 50 A as NM-B cable or 60 A as THHN in conduit. Long runs need a bigger size for voltage drop.

Copper wire gauge chart

AWG60 °C75 °C90 °CBreaker, 60 °CBreaker, 75 °CRun at 240 V
1415 A20 A25 A15 A15 A76 ft
1220 A25 A30 A20 A20 A90 ft
1030 A35 A40 A30 A30 A96 ft
840 A50 A55 A40 A50 A92 ft
655 A65 A75 A50 A60 A122 ft
470 A85 A95 A70 A80 A146 ft
385 A100 A115 A80 A100 A146 ft
295 A115 A130 A90 A110 A168 ft
1110 A130 A145 A110 A125 A187 ft
1/0125 A150 A170 A125 A150 A196 ft
2/0145 A175 A195 A125 A175 A212 ft
3/0165 A200 A225 A150 A200 A234 ft
4/0195 A230 A260 A175 A200 A296 ft

Aluminum wire gauge chart

AWG60 °C75 °C90 °CBreaker, 60 °CBreaker, 75 °CRun at 240 V
1215 A20 A25 A15 A15 A73 ft
1025 A30 A35 A25 A25 A70 ft
835 A40 A45 A35 A40 A70 ft
640 A50 A55 A40 A50 A89 ft
455 A65 A75 A50 A60 A118 ft
365 A75 A85 A60 A70 A127 ft
275 A90 A100 A70 A90 A125 ft
185 A100 A115 A80 A100 A142 ft
1/0100 A120 A135 A100 A110 A162 ft
2/0115 A135 A150 A110 A125 A181 ft
3/0130 A155 A175 A125 A150 A190 ft
4/0150 A180 A205 A150 A175 A205 ft

How to read it

Ampacity is what the wire can carry at each insulation temperature rating, with no more than 3 current-carrying wires together and 86 °F around them. NM-B cable (Romex) and UF-B have to use the 60 °C column, and NM-B is only made in copper, 14 to 2 AWG. THHN in conduit uses 75 °C, the most a breaker's terminals are rated for. The breaker columns are the biggest standard breaker at or under each ampacity. 14, 12 and 10 AWG copper are capped at 15, 20 and 30 A whatever the column says.

Run at 240 V is the longest one-way distance before a load at the full 75 °C breaker drops more than 3%. Half the load runs twice as far; 120 V runs half as far. For your own load and distance, use the wire size calculator. Don't know the amps? Watts to amps.

A load that runs 3 hours or more, like an EV charger or a heater, counts at 125%. A 48 A charger needs a 60 A breaker.

Where the numbers come from